PUE Calculation Formula The PUE ranges from 1 to 3. If the PUE value is greater than or equal to 3, the value is displayed as 3. When the PUE value is 1, it is invalid. Table 6-44 PUE calculation formula Configuration Mode PUE Calculation Method Standard PUE = Increment in total...
The ECC800-Pro connects to the NetEco over a northbound port and can upload the calculated PUE and power consumption data to the NetEco. PUE Calculation Formula The PUE ranges from 1 to 3. If the PUE value is greater than or equal to 3, the value is displayed as 3. When the PUE ...
PUE is calculated using this straightforward formula: PUE = Total Facility Energy / IT Equipment Energy Note that total facility energy includes lighting, cooling, and other noncomputing functions. With this, PUE can quantify how much energy is used for the overall operation of a data center ...
微模块系统的PUE值计算 1 PUE 定义 电能使用效率PUE(Power Usage Effectiveness)是评价数据中心能源效率的指标,是数据中心消耗的所有能源与IT 负载使用的能源之比。 PUE=数据中心总设备能耗/IT 设备能耗,PUE 是一个比值。PUE 值越接近于1,表示一个数据中心的绿色化程度越高。2 PUE 公式 其中网络IT 机柜20个...
The formula has to be used to determine the efficiency of a particular data center over time, not to compare different ones. To make it clear, I would like to introduce an example of PUE calculating: Let’s say that the total facility energy of a data center is 12.000 MWh and the IT...
According to the instantaneous PUE calculation formula, instantaneous PUE = Total system input power/Current IT load power = 100/90 = 1.11.Configuring Instantaneous PUE User-defined Mode Context The following table describes functions of configuration buttons for the instantaneous PUE user-defined mode....
According to the instantaneous PUE calculation formula, instantaneous PUE = Total system input power/Current IT load power = 100/90 = 1.11.Configuring Instantaneous PUE User-defined Mode Context The following table describes functions of configuration buttons for the instantaneous PUE user-defined mode....
The ECC800-Pro connects to the NetEco over a northbound port and can upload the calculated PUE and power consumption data to the NetEco. PUE Calculation Formula The PUE ranges from 1 to 3. If the PUE value is greater than or equal to 3, the value is displayed as 3. When the PUE ...
You can calculate the PUE based on the PUE calculation formula. Procedure Log in to the ECC800-Pro WebUI as an administrator. Choose System Settings > PUE Configuration > PUE Configuration . Set PUE function to Enable. Choose System Settings > PUE Configuration > PUE. Set PUE configuration ...
According to the instantaneous PUE calculation formula, instantaneous PUE = Total system input power/Current IT load power = 100/90 = 1.11.Configuring Instantaneous PUE User-defined Mode Context The following table describes functions of configuration buttons for the instantaneous PUE user-defined mode....