Cable type Plastic (POF) PCF Glass Transmission rate in Mbit/s 9.6 to 1500 and 12000 9.6 to 1500 and 12000 9.6 to 12000 Max. length between two stations in m 50 300 2850 (for 62.5/125 fiber; 3.5 dB/km) For further details about the bus connectors and cables require...
BaudRateBittime(tBit)Maxcablelength(typeA)9,6kBit/s104,2us1200m19,2kBit/s52,1us1200m31,25kBit/s32us1200m45,45kBit/s22us1200m93,75kBit/s10,7us1200m187,5kBit/s5,3us1000m500kBit/s2us400m1500kBit/s666,7ns200m3000kBit/s333,3ns100m...
4.Connectthecableaccordingtotheelectricalconnectiondiagram (seeFigurebelowordiagraminthescrewcover). 5.Screwontheconnectionhousinghcoveragainsecurely.TightentheAllenscrews ofthesafetygripsecurely. ➀ ENDRESS+HAUSER PROMASS 3s E-+ ➂ cablelength➃ max.20m➁➄Transmitter connectionhousing 7 6 y 3 3...
2016 Parker Hannifin Manufacturing Ltd.All rights strictly reserved. No part of this document may be stored in a retrieval system, or transmitted in any form or by any means to persons not employed by a Parker SSD Drives company without written permission from Parker Automation Wuxi, a division...
30.09.2009 Page 1 C-DIAS Profibus DP Slave module CPB 021 The C-DIAS Profibus DP slave module CPB 021 serves as an interface module between the C-DIAS control system and Profibus. This module supports a galvanically separated Profibus slave. Technical Data Performance data
8 MG.90.A4.02 – VLT is a registered Danfoss trademark FCM 300 / FCD 300 / VLT 2800 /DPV1 PROFIBUS The total drop cable length for one segment is limited - Capacity: 30 pF/m T h as stated in the table below. - Damping: max. 9 dB over the whole wire e P R length O Drop ...
Wave length860 nm Optical input powermin. -28 dBm, max. -3 dBm Launchable optical powerin multi-mode fiber (50/125): (50/125): -15 dBm (62,5/125): - 13 dBm Cable lengthMulti-mode fiber (MM) 50/125: 3 km with A = 3 dB/km; 3 dB buffer ...
The available data rates depend on the type of cable and total cable length used on the network: Baud Rate 9.6 K 19.2 K 45.45 K 93.75 K 187.5 K 500 K 1.5 M 3M 6M 12 M Maximum Cable Length 1000 m 1000 m 1000 m 1000 m 1000 m 400 m 200 m 100 m 100 m 100 m Datalink - A...
or PCF FO cable (max. length 300 m). The FO cables have two simplex connectors fitted at both ends. The FO connection between two devices is established by the optical transmitter of one device being connected to the optical receiver of the other device via a fiber, while the optical rece...
Cable lengthmax. 10 m Sensor typestype J, K, mV measurement Measuring rangetype J: -10…+900°C; type K: -100…+1370°C Resolution0.1°C per digit Conversion timeapprox. 250 ms Measurement error/uncertainty< ±0.5% (of the full scale value) ...