Connection to triggering devices must be made within 20ft of distance and using conduit for wiring. 3- Auxiliary output (-AUX+) 24VDC at 1A max. 4- AC Local [NC, NO, C] should connect to the host control panel for local annunciation of the trouble condition. If common trouble input, ...
The test sequence may be as follows: (1) disconnect NAC wiring from the control panel (such as disconnect wiring at output terminals 3 and 4); (2) connect NAC wiring to handheld diagnostic tool; (3) run the test software on the diagnostic tool (including reducing the voltage to the NAC...