COP = 12 / (kW/ton) / 3.412 EER = 12 / (kW/ton) EER = COP x 3.412 If the efficiency of a chiller is rated to 1 kW/ton, then COP = 3.52 EER = 12 Cooling Load in - kW/ton The term kW/ton is commonly used for larger commercial and industrial air-conditioning, he...
Energy units conversion from, hp/h ( horse power per hour ) to kw/h ( kilo-watt per hour ) and into BTU ( British Thermal Unit ) outcomes. Is 1.0hp/h (horsepower-hour) = 0.75kW/h (kilowatt-hour)? Energy Unit Convert: 1 horsepower hour ( hp-h ), ...
ACH = CFM x 60/Area x Heightceiling Total Heat (BTU/hr.) = 4.5 x CFM x Δh (std. air) Sensible Heat (BTU/hr) = 1.1 x CFM x Δt (std. air) Latent Heat (BTU/hr) = 0.69 x CFM x Δgr. (std. air) 1 HP = 746 Watts 1 kW = 3413 BTU...